UV-12-S/UV-156-S

Technical Specification
- Working Based on Bernoulli’s Theorem
- Hardened disc to withstand continous water hammering
- All Stainless Steel construction – better mechanical properties
- Seat integral with the body – No possibilities of leakage from joints
- Inbuilt Strainer – Avoids Clogging
Steam
Size | A | L | H1~ | H2~ |
15 | ½”BSP | 80 | 52.5 | 53.6 |
20 | ¾”BSP | 92 | 60 | 61.3 |
25 | 1” BSP | 108 | 69.5 | 72.2 |
Size | A | L | H1~ | H2~ |
15 | ½”BSP | 78 | 44 | 60 |
20 | ¾”BSP | 78 | 44 | 60 |
25 | 1” BSP | 84 | 54 | 70 |
Working Pressure | Max B.O.P 17.24 Bar at 225℃ |
Test Pressure | Shell Pressure 34.4 Bar Hyd. |
End Details | Screwed Female BSP Parallel Threads to BS:21 |
Working Pressure | Max B.O.P 31 Bar at 425℃ |
Test Pressure | Shell Pressure 62 Bar Hyd. |
End Details | Screwed Female BSP Parallel Threads to BS:21 |
The Trap should be installed horizontally with flow direction as indicated on the valve . the trap should be below the drainage point of the equipment. Float always rises & falls vertically in horizontal plane. For correct working of trap, the arrow on the name plate should be indicating in vertically downwards direction.
Thermodynamic Steam Trap 4.13 MB
Document No: UV-12-S/UV-156-S